November 9, 2011
Facility
Monitoring
Presented by:
Chris Ihfe
Przeglądanie stron 0
1 2 3 4 5 6 ... 60 61

Podsumowanie treści

Strona 1 - Monitoring

1www.rletech.comNovember 9, 2011Facility MonitoringPresented by:Chris Ihfe

Strona 2 - Product lines include:

10www.rletech.comLeak Detection Cables• Designed for open areas and to encapsulate areas of concern• Unique Sensing Cables to detect:– Conductive f

Strona 3 - 27% 15% 11% 9% 4%

11www.rletech.comLeak Detection Cable (SC)• Detects any conductive fluid• Patented design• Quick dry / quick reset• Plenum rated – CL2P• For use

Strona 4

12www.rletech.comLeak Detection Cable (SC-H)• Hydrocarbon (liquid fuel) detection cable• Other fluids will not create an alarm condition• Current d

Strona 5

13www.rletech.comLeak Detection Cable (SC-C)• Chemical Sensing Cable• Used to detect:– Acids– Bases– Other conductive harmful fluids• Can be cle

Strona 6 - The Impacts of Downtime

14www.rletech.comZone Controllers• Ideal for Sensing Cable installed in open areas where the Sensing Cable is visible• Identifies that fluid is in c

Strona 7 - Leak Detection

15www.rletech.comSingle Zone ControllersNovember 9, 2011LD300 LD1000EnclosurePlastic MetalPowerrequirements5VDC 24VACorDCMax.SensingCable300ft/9

Strona 8 - Spot Detectors

16www.rletech.comMultiple Zone ControllersNovember 9, 2011LDRA6EnclosureMetalPowerrequirements24VACorDCInputs6SensingCablemax.length1000ft/305m

Strona 9

17www.rletech.comDistance Read Controllers• Ideal for longer runs of Sensing Cable and Sensing Cable installed in concealed areas• Identifies the lo

Strona 10 - Leak Detection Cables

18www.rletech.comDistance Read ControllersNovember 9, 2011SeaHawk 10K LD1500 LD2100 LD5100Maximumsensingcable 10,000ft/3048m* 1,500ft/457m 5,000ft

Strona 11 - Leak Detection Cable (SC)

19www.rletech.comSeaHawk Virtual / Physical ZonesNovember 9, 2011(Available only on the LD2100 & LD5100)Virtual Zones•Distance to the leak determi

Strona 12 - Leak Detection Cable (SC-H)

2www.rletech.com• Established in 1984• Focused on developing equipment to help minimize downtime• Standard, Scalable & Custom Solutions• Produ

Strona 13 - Leak Detection Cable (SC-C)

20www.rletech.comSeaHawk AccessoriesNovember 9, 2011FM1114WCCS-50J-clips (JC-xxx)X-CONLD-ENC/-NPNon Sensing Cable (NSC)

Strona 14 - Zone Controllers

21www.rletech.comSeaHawk AccessoriesNovember 9, 2011• Non-sensing cable (NSC-xx)– Used between lengths of sensing cable– Does not add resistance• J

Strona 15 - Single Zone Controllers

22www.rletech.comSeaHawk AccessoriesNovember 9, 2011• Weighed cable connector (WCCS-50)– Creates distinct separation between lengths of Sensing Cabl

Strona 16 - Multiple Zone Controllers

23www.rletech.comNovember 9, 2011Alarm Monitoring & Notification Products

Strona 17 - Distance Read Controllers

24www.rletech.comAlarm monitoring and notification products• Stand-alone appliance and easily integrated• No recurring costs• Scalable• In-band an

Strona 18

25www.rletech.comNovember 9, 2011• Stand-alone monitoring appliance with redundant direct alarm notification- In-band (network)- Out-of-band (optio

Strona 19 - Physical Zones

26www.rletech.comWhat can Falcon products monitor?November 9, 2011Any device that provides any of the following output signals: Dry Contact, 4-20mA, 0

Strona 20 - SeaHawk Accessories

27www.rletech.comWhat can Falcon products monitor?November 9, 2011Any device that provides any of the following output signals: Dry Contact, 4-20mA, 0

Strona 21

28www.rletech.comHow are alerts sent?November 9, 2011F110 Wirelessgateway F3400 FMSDirectNotification– Network*Singleemailaddress(ordistro list

Strona 22

29www.rletech.comInput detailsNovember 9, 2011F110 Wireless GatewayF3400 FMSProprietarysensors3inputsfor temperatureor temperature/ humidity

Strona 23 - November 9, 2011

3www.rletech.comLeading Causes of Business Downtime*November 9, 2011*Source: Contingency Planning Research, a division of Eagle Rock Alliance0%5%10%15

Strona 24 - Scalable

30www.rletech.comFalcon FMS – Web InterfaceAlarm Status:• Unique input labels can be displayed for alarm and normal conditions• Labels are color cod

Strona 25 - Falcon FMS

31www.rletech.comFalcon FMS – Web InterfaceIP Linking:• Up to 10 IP links can be integrated on the main page.• The image is a link to open up the IP

Strona 26 - Existing Sensors including:

32www.rletech.comFalcon FMS – Web InterfaceSimplified Power Monitoring:• Monitor the main power feeds and/or each individual circuit• Alarm threshol

Strona 27 - Existing Equipment including:

33www.rletech.comFalcon FMS – Web InterfaceLinks to Graphical User Interface:• Floor plan can be uploaded to the FMS as a .jpg file• Integrated inpu

Strona 28 - How are alerts sent?

34www.rletech.comNovember 9, 2011Falcon FMS – Custom Map

Strona 29 - Input details

35www.rletech.comFalcon FMS – Custom MapFMS GUI: • Can display up to 284 inputs (104 directs inputs + 180 Modbus or SNMP values)• The size of the im

Strona 30 - Falcon FMS – Web Interface

36www.rletech.comFalcon FMS – “Nest”View multiple RLE products on a single page:• Displays the status from as many as 32 Falcon products and/or SeaHa

Strona 31

37www.rletech.comFalcon FMS – “Nest” MapA .jpg image (map) can be uploaded as a background image•Integrated products displayed as color coded points o

Strona 32

38www.rletech.comFalcon FMS – PDA ViewAlarm statuses can also be viewed with a PDA or mobile deviceNovember 9, 2011

Strona 33

39www.rletech.comFalcon FMS – Data LoggingInternal logs stored in non-volatile memory• Last 256 alarms – Color coded to identify:– Acknowledged– Un

Strona 34 - Falcon FMS – Custom Map

4www.rletech.comLeading Causes of Business Downtime*November 9, 20110%5%10%15%20%25%30%Power OutageWater DamageHardware FailureEarthquake Fire Hurrica

Strona 35

40www.rletech.comFalcon FMS – Data Logging GraphInternal logging:• Stored on the FMS – no external software required• Available as a graph or downlo

Strona 36 - Falcon FMS – “Nest”

41www.rletech.comFalcon FMS – Input Configuration PageSimple Configuration:• Drop down menus to select input types• Multiple alarm thresholds• Desc

Strona 37 - Falcon FMS – “Nest” Map

42www.rletech.comFalcon FMS – SchedulesTwo configurable schedules:• Controls the relay outputs and commonly used to turn equipment on/off• Identify

Strona 38 - Falcon FMS – PDA View

43www.rletech.comFalcon FMS – InputsHardwired Inputs:• Dry Contacts, 4-20mA, 0-5VDC and 0-10VDC signals• Scalable from 8 to104• No proprietary conn

Strona 39 - Falcon FMS – Data Logging

44www.rletech.comFalcon FMS – ExpansionFMS Enclosures:FMS-x (1RU) 8 Inputs, each selectable as NO/NC Dry Contact or 4-20mA2 NO/NC Dry Contact outputs

Strona 40 - Internal logging:

45www.rletech.comFalcon FMS – Expansion OptionsFMS Expansion Cards:EXP-A-24/48 12 Inputs, each configurable to accept- Digital Dry Contact input- 4

Strona 41 - Each Input:

46www.rletech.comFalcon FMS – OutputsDry Contact, Form “C” Relay Outputs:• Scalable from 2 to 34• Event driven– By alarm conditions exceeding accep

Strona 42 - Falcon FMS – Schedules

47www.rletech.comFalcon FMS – Access• All information can be viewed and the FMS can be configured with a Web Browser– Access through network– Acces

Strona 43 - Falcon FMS – Inputs

48www.rletech.com• A receiver for up to 400 418MHz / 900MHz wireless devices• Provides direct alarm notification (4 email addresses)• Protocols for

Strona 44 - Falcon FMS – Expansion

49www.rletech.comCan be used as a Network router sending signals to a centralized unit for a single view of multiple units.Wireless Gateway – FDS-WiNo

Strona 45 - FMS Internal Modem Option:

5www.rletech.comSite Monitoring Best Practices• Identify issues before they become critical!– Snowballing effect – Issues usually start small– Loca

Strona 46 - Falcon FMS – Outputs

50www.rletech.com• Maximum integrated transmitters:– Without a Point Repeater – 100– With use of a Point Repeater – an additional 300• Wireless dis

Strona 47 - Falcon FMS – Access

51www.rletech.comSite Monitoring - Reactive• Facility lost one of the three phases of utility power• Computer Room Air A/C units continued to run un

Strona 48 - Wireless Gateway – FDS-Wi

52www.rletech.comSite Monitoring Best Practices - Proactive• Power meters installed on the utility feed• Intelligent information pulled from the CRA

Strona 49

53www.rletech.comSite Monitoring - Reactive• Generator block heater stuck on• Normal average is 120 degrees when not running• Block reached 150 deg

Strona 50

54www.rletech.comSite Monitoring Best Practices - Proactive• Generator alarms integrated into a monitoring system• Alarms trigger when temperatures

Strona 51 - Site Monitoring - Reactive

55www.rletech.comThe Falcon SolutionNovember 9, 2011• Direct alarm notification ensures that the right people are aware of issues before they become

Strona 52

56www.rletech.comFalcon alarm monitoring & notificationNovember 9, 2011• Even equipment with no alarming capabilities can easily be retrofitted t

Strona 53

57www.rletech.comSite Monitoring• Every site is unique• Understand budget restrictions• Establish immediate needs• Identify long term goals• Know

Strona 54

58www.rletech.comFalcon alarm monitoring & notificationNovember 9, 2011• Are all available sensors and alarm signals integrated into an alarm not

Strona 55 - The Falcon Solution

59www.rletech.comSite Monitoring Best Practices• Integrate all existing equipment and sensors– Summary alarm outputs are available from most critica

Strona 56

6www.rletech.comThe Impacts of Downtime• Redirection of efforts towards recovery• Employee productivity and moral• Customer ConfidenceNovember 9, 2

Strona 57 - Site Monitoring

60www.rletech.comNovember 9, 2011• Vendor neutral systems that simplify designing the best solution• Eliminate recurring costs • A cost effective w

Strona 58 - – Is it scalable

61www.rletech.comNovember 9, 2011Alarm Monitoring & Notification ProductsQuestions?

Strona 59

7www.rletech.comNovember 9, 2011Leak Detection

Strona 60 - Falcon Products

8www.rletech.comSpot Detectors• Designed for confined areas• Potted electronics = submersible design• Corrosion resistant, no exposed metal• No vi

Strona 61 - Questions?

9www.rletech.comSpot DetectorsNovember 9, 2011SD‐RO1 SD SD‐Z SD‐Z1Power24VAC/DC* Falcon SeaHawk controller SeaHawk controllerAudible‐ ‐ ‐ ‐OutputForm